0803UDSA-2GBEN, Pag. 1/36
0803UDSA-2GBEN
UDSA 008-2 / 100-2
Gas fired Balanced flue / Fan assisted flue
unit heater
INSTALLATION
COMMISSIONING
SERVICING
These appliances meet the following EC Directives:
DIR CE 90/396/EEG:GAD
DIR CE 89/336/EEG:EMC
DIR 73/23/EEG:LVD
DIR 89/392/EEG:MD
®
Reznor U.K. Limited - Park Farm Road - Folkestone - Kent - England
Tel.: 01303-259141 · Fax 01303-850002
WARNING
Please read this document carefully before commencing installation, commissioning and/or servicing.
Leave it with the user or attached to the appliance or gas service meter after installation.
Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death. All
work must be carried out by appropriately qualified persons.
The manufacturer does not take any responsibility in the event of non-observance of the regulations concerning the
connection of the apparatus causing an evil operation possibly resulting in damage to the apparatus and/or
environment in which the unit is installed.
Vue de la page 0
1 2 3 4 5 6 ... 35 36

Résumé du contenu

Page 1 - UDSA 008-2 / 100-2

0803UDSA-2GBEN, Pag. 1/360803UDSA-2GBENUDSA 008-2 / 100-2Gas fired Balanced flue / Fan assisted flueunit heaterINSTALLATIONCOMMISSIONINGSERVICINGThese

Page 2 - 0803UDSA-2GBEN, Pag. 2/36

0803UDSA-2GBEN, Pag. 10/36Figure 3 :Type B appliances : Combustion air and flue pipe sockets1) Flue pipe outlet collar2) Combustion air inlet openinga

Page 3 - Warnings

0803UDSA-2GBEN, Pag. 11/36Figure 5 : Type C appliances : Combustion air and flue pipe sockets Combustion air inletpipe & flue pipe forbalanced

Page 4 - 0803UDSA-2GBEN, Pag. 4/36

0803UDSA-2GBEN, Pag. 12/36The presence of chlorine vapours in the combustion air of gas-fired heating equip-ment presents a potential corrosion hazard

Page 5 - Rear view

0803UDSA-2GBEN, Pag. 13/369. Hanging the heaterWarning : Do not place or add additional weight to the suspended heater.Before suspending the heate

Page 6 - Table 3 :

0803UDSA-2GBEN, Pag. 14/36Figure 7 :Wall bracket kits (optional)Types 008-2 -> 030-2When desired the heaters may be supported by wall brackets. Su

Page 7 - 6. Technical data

0803UDSA-2GBEN, Pag. 15/36All piping must be in accordance with requirements outlined in the National GasCodes (different for each country). Gas suppl

Page 8 - 7. Flue

0803UDSA-2GBEN, Pag. 16/3611. Electricalsupply andconnectionsThe electrical installation may only be carried out by an appropriately qualifiedperson c

Page 9 - Flue outlet

0803UDSA-2GBEN, Pag. 17/36Figure 9 : Wiring connections on the terminal board

Page 10 - Air supply

0803UDSA-2GBEN, Pag. 18/3612. Check in-stallation&start-upCheck the instal-lation prior tostart-upHeater start-up Check suspension. Unit must

Page 11 - Combustion air inlet

0803UDSA-2GBEN, Pag. 19/36Operating instructionsand operating sequenceCheck installation afterstart-up1. Set thermostat to the lowest setting. 2.

Page 12 - 8. Location heater

0803UDSA-2GBEN, Pag. 2/36INDEXWarnings ...

Page 13 - the heater

0803UDSA-2GBEN, Pag. 20/36Burner gas pressureadjustmentThe gas pressure is set for the required heat input before the appliance leaves thefactory. Pr

Page 14 - Wall bracket kits (optional)

0803UDSA-2GBEN, Pag. 21/36Figure 10b : HONEYWELL gas valve (type 035-2 -> 100-2)Table 8 : Burner jets and pressures26314578Legend1) Gas inlet2) Ga

Page 15 - 10. Gas Piping and

0803UDSA-2GBEN, Pag. 22/36DefinitionsStart position: The system is not in lock-out position and can proceed with the start-up sequence upon a demand f

Page 16 - 11. Electrical

0803UDSA-2GBEN, Pag. 23/3613. Maintenance & ServiceMaintentance Sched-uleNOTE: If replacementparts are required, use onlyfactory-authorized

Page 17 - 0803UDSA-2GBEN, Pag. 17/36

0803UDSA-2GBEN, Pag. 24/36Figure 11b - Control panelassy located on a removablebracketLegend:15) Control relay (ER)16) Terminal blocks17) 2 stage burn

Page 18 - 12. Check in

0803UDSA-2GBEN, Pag. 25/3615. Burner MaintenanceThis heater has a unique one-piece T-CORE2® burner assembly designed to pro-vide controlled flame

Page 19 - Check installation after

0803UDSA-2GBEN, Pag. 26/366. Remove burnera) Locate the burner body front support. Removethe screws that attach it to the secondary airshield. Refer

Page 20 - Burner gas pressure

0803UDSA-2GBEN, Pag. 27/36Inspect and clean the burnerReinstall the burnerRepeat ‘Burner removal’ steps above in the opposite order.Ignitor - Refer to

Page 21 - 0803UDSA-2GBEN, Pag. 21/36

0803UDSA-2GBEN, Pag. 28/36Figure 17 - Control relayFlame sensor - Refer to figure 11a and locate the flame sensor. Disconnect thewire, remove the scr

Page 22 - Sequence

0803UDSA-2GBEN, Pag. 29/3620. Venter motor & wheelFigure 18 - Fan blade positionon the motor shaft3. Remove the fan assembly (fan guard, moto

Page 23 - Maintentance Sched

0803UDSA-2GBEN, Pag. 3/36FOR YOUR SAFETYWhat to do if you smell gas:• Do not try to light any appliance.• Do not touch any electrical switch; do not u

Page 24 - Maintenance

0803UDSA-2GBEN, Pag. 30/36Venter wheel position onshaftFigure 19UDSA models 008-2 - 020-2(Rotation clockwise from motor shaft end)UDSA models 025-2

Page 25 - 15. Burner

0803UDSA-2GBEN, Pag. 31/3621. Operating gas valveFigure 22Gas valve(UDSA models 008-2 - 030-2)Figure 23Gas valve(UDSA models 035-2 - 100-2)WARNIN

Page 26 - Figure 13b

0803UDSA-2GBEN, Pag. 32/3623. Limit controlsIf a limit control needs replacing,use only the factory authorized re-placement part for the size ofheat

Page 27 - 16. Burner orifice

0803UDSA-2GBEN, Pag. 33/3625. Trouble-The integrated control relay monitors the operation of the heater. If theheater fails to operate properly, rev

Page 28 - 0803UDSA-2GBEN, Pag. 28/36

0803UDSA-2GBEN, Pag. 34/36YESYESYES NOYESNO YE S NOYESNOYESNOTrial for ignitionCall for heatIs there a spark across gap at igniter? Does gas ignite?I

Page 29 - Table 9 : Dimensions A

0803UDSA-2GBEN, Pag. 35/36General TroubleshootingPROBLEM PROBABLE CAUSE REMEDY1. No power to unit. 1. Turn on power, check supply fuses or circuit bre

Page 30 - Figure 20

0803UDSA-2GBEN, Pag. 36/36Subject to modifications26. Parts listDescriptionApplicationUDSA-2 Partnumber (PN)Control relay 008 … 100 03 25322Spark ig

Page 31 - gas valve

0803UDSA-2GBEN, Pag. 4/363. Warranty4. UncratingandpreparationWarranty is void if :a. Wiring is not in accordance with the diagram furnished with th

Page 32 - 22. Combustion

0803UDSA-2GBEN, Pag. 5/365. Dimensions & Clearances (horizontal orientation=standard) Top view Front viewLegend:1.

Page 33 -

0803UDSA-2GBEN, Pag. 6/36Clearances (mm)Units must be installed so that the minimum clearances in the following table areprovided for combustion air s

Page 34 - 0803UDSA-2GBEN, Pag. 34/36

0803UDSA-2GBEN, Pag. 7/366. Technical dataTable 4 : Technical data1) Gas Appliance Classifications for Approved Venting Methods based on CEN-report

Page 35 - General Troubleshooting

0803UDSA-2GBEN, Pag. 8/367. FluerequirementsModel UDSA-2 heaters may be installed as Type-B and Type-C installations.Flue must be in accordance with

Page 36 - 26. Parts list

0803UDSA-2GBEN, Pag. 9/36 Flues for powervented installations(type B appliances)Figure 2 : Approved appliances type BB22 - roof Flue outletVente