Please read this information thoroughly and become familiar with the capabilities and use of your appliance before attempting to operate or maintain t
10Example:AB = 451VBC = 460VAC = 453V2. Determine the average voltage in the power supply.3. Determine the maximum deviation:4. Determine percent o
11To set the cycle timer, place the timing pin on the defrost control board to the desired time interval post. NOTE: All units are shipped from the fa
12START UP & ADJUSTMENTSPre-Start Check List Verify the unit is level and allows condensate to drain. Verify the outdoor coil and top of the u
13After refrigerant line connections are completed, it is required that you leak check and evacuate the indoor section and all line connections (using
14Table 3. Unit Dimensions & Shipping WeightsDefrost Control BoardThis control includes - 5 minute anti-short cycle timer protection for Stage 1 H
15ELECTRICAL INFORMATIONModelNumberT5BP-090C 090D 120C 120D208-230V 460V 208-230V 460V920892 920893 920894 920895PERFORMANCE DATAGross Cooling Capacit
16Figure 6. T5BP Wiring Diagram710969009/09FIELD WIRINGLEGEND:LOW VOLTAGEHIGH VOLTAGE¢710969V¤Commercial Split System Heat PumpThree PhaseNOTES:1. Dis
17Figure 7. Typical Heat Pump Thermostat ConnectionsBLOWERMOTERGNDBLACKBLACKGREENBROWNTO FIELDSUPPLIED DISCONNECTSINGLE STAGEHEAT PUMP THERMOSTATOUTDO
18T5BP CHARGING CHARTS - COOLING ONLYApplication Notes on the Use of Charging Charts• This equipment’s cooling system contains refrigerant under high
19Liquid Temperature (° F)Liquid Pressure (psig)17520022525027530032535037540042545047550052555 60 65 70 75 80 85 90 95 100 105 110 115 120 125T5BP Ch
20T5BP HEAT MODE VERIFICATION CHARTS - HEATING ONLY• Read all notes and warnings for the Cooling-mode charging charts prior to using these Heating-mo
21Figure 11. Verifi cation Chart for 10 ton units20025030035040070.0 75.0 80.0 85.0 90.0 95.0 100.0 105.0 110.0 115.0 120.0Liquid Temperature (° F)Liqu
7090940 Specifi cations and illustrations subject to change without notice or incurring obligations. Printed in U.S.A. (01/10)7090940O'Fallon, MO
3Important Safety Information ...6Heat Pump Installation ...7 Before You
4ABOUT THE HEAT PUMPYour heat pump is a unique, all weather comfort-control appliance that will heat and cool your home year round and provide energy
5At the beginning of the defrost cycle, both the outdoor condenser fan and compressor will turn off. After approximately 30 seconds, the compressor wi
6INSTALLER INFORMATIONIMPORTANT SAFETY INFORMATIONPlease read all instructions before servicing this equipment. Pay attention to all safety warnings a
7HEAT PUMP INSTALLATIONGeneral InformationThe T5BP series heat pump is designed only for outdoor rooftop or ground level installations. This unit has
82”Figure 3. Ground Level InstallationGround LevelGround level installations must be located according to local building codes or ordinances and these
9connections in accordance with all applicable codes and ordinances.• Overcurrent protection must be provided at the branch circuit distribution pane