Form I-RA/D 140/235 (Version A), Mfg No. 110318 Rev 3, Page 15
Vent Cap
Factory Built Vent
8 ft (2.4M)
Minimum
Single Wall Pipe
Barometric Draft
Regulator
(alternate location)
Tee with
Cleanout
Barometric
Draft
Regulator
Draft Inducer
(if required)
Factory Built Vent
Roof jack recommended by the
manufacturer of the factory built vent
3 ft (914mm)
minimum
2 ft (6.0mm)
minimum
Ventilated Thimble
if construction
is combustible
Single Wall Pipe or
Factory Built Vent
Detailed Require-
ments for the Vent
System (read all
before beginning
installation)
Any portion of the vent
system that passes
through an unheated
space or a concealed
area such as an “attic”
must be a factory-built
vent that is approved to
Standard UL 641. See
illustration . .
. . . . . . . . .
The heater may be
vented into a masonry
chimney that complies
with the BOCA Na-
tional Mechanical Code
for low-heat appliances
or other building code
requirements for low-
heat appliances.
Pipe/Joints/Clearances: Single-wall pipe must be a minimum of 24
gauge galvanized steel for 8” or 9” diameter pipe and 22 gauge for 10”
or 12” diameter pipe. Each joint must be secured with three screws or
rivets. If installing a factory-built vent, follow the manufacturers
instructions.
If the vent system passes through a combustible wall, material or roof,
for single wall pipe, maintain 18” (457mm) clearance or install a
ventilated thimble that is not less than 12” (305mm) larger than the
diameter of the vent pipe. If installing factory-built vent, follow the
manufacturers instructions.
Horizontal Length and Slope: The horizontal portion of the vent
must comply with the maximum horizontal length shown in the table
below and have not more than two elbows. Horizontal portions must
be sloped upward 1/4” for each foot of pipe. If installation conditions
require horizontal lengths in excess of those permitted in the table, a
draft inducer must be used.
Vent Pipe Model Size and Maximum Length
Diameter Vertical Length of Horizontal Pipe
8” 140 with 8 feet (2.4M) or Equal to or less than
more of vertical pipe the vertical height
8” 235 with 8 feet (2.4M) 4 feet (1.2M) or less
of vertical pipe
8” 235 with 10 feet (3M) Equal to or less than
of vertical pipe the vertical height
Vent Size: The vent system must be at least 8” in diameter.