Reznor RA 140 Guide de dépannage Page 24

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 52
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 23
Form I-RA/D 140/235 (Version A), Page 24
Backflow
Sensor
Switch on
Viewport Door
General
Maintenance
Requirements
WARNING: Turn off electric power to the unit before
doing any service or maintenance on the heater.
When burning used automotive diesel and truck oils, this heater will re-
quire more frequent service than conventional heating equipment. All used
oils contain a small amount of ash. This ash is similar in texture to that
found in wood burning fireplaces, and varies with the types of oil used.
FAILURE TO REMOVE THIS ASH ON A REGULAR BASIS WILL
VOID THE WARRANTY.
Do not let your oil supply tank run out of fuel. Check the oil level in the
supply tank daily to be certain an adequate supply is available. Running out
of fuel will require you to re-prime the system.
The following are starting points for tailoring a maintenance schedule to fit
the application. When performing the maintenance procedures listed be-
low, note the hours on the hour meter. After one or two cleanings, the main-
tenance schedule may be altered based on the hours of operation. However,
if there is a major change in the type of used oil being burned, maintenance
requirements can be affected. Any time there is a major change in fuel,
return to the schedule listed below and note the hour meter readings to re-
tailor the maintenance schedule.
At the end of the heating season or whenever the heater will be shut
down for a long period, always turn off the power. Clean the heat ex-
changer/combustion chamber and the flue pipe. Before restarting, perform
all maintenance checks.
Weekly:
Check the vacuum gauge on the filter for an indication that the oil
line filter needs replaced and/or motor pump screen needs cleaning.
The maximum vacuum rise is 10”Hg; the maximum reading is
15”Hg.
Inspect the combustion chamber and heat exchanger tubes. If
cleaning is needed, follow the instructions on page 28.
Record the hour meter reading for future reference. A Maintenance
Record Chart is provided in the Appendix for this record.
WARNING: Wear protective clothing, including gloves
and a face mask or respirator. Dispose of ash properly.
See the warning statement on cleaning the combustion
chamber.
Monthly:
Drain water from the bottom of the supply tank until a steady
stream of oil is obtained.
Clean the backflow/ash sensor switch. Remove any soot from the
sensor. Check the electrical connections.
Maintenance
Maintenance
Schedule
Vue de la page 23
1 2 ... 19 20 21 22 23 24 25 26 27 28 29 ... 51 52

Commentaires sur ces manuels

Pas de commentaire