Reznor RA 140 Guide de dépannage Page 42

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 52
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 41
Form I-RA/D 140/235 (Version A), Page 42
Troubleshooting Continued
Check for line
voltage across Terminals
8 and 11. Is voltage
read?
Is ignition
transformer producing
spark?
Is
electrode position
correct?
Check for line
voltage across Terminals
12 and 11. Is voltage
read?
Check oil delivery
system.
Is pressure of
compressed air as
required?
Replace air pressure
switch located in the
main junction box.
Remove air filter and
operate the burner motor.
Check for line
voltage across Terminals
12 and 11. Is voltage
read?
Install new
air filter.
Are there
leaks in the air
connections or
lines?
Replace air tubing
and tighten
connections.
Rebuild
compressor.
Adjust
electrodes.
Are
electrodes and
insulators OK?
Replace ignition
transformer.
Replace electrode
assembly.
Replace ignition
controller.
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO YES
NO
YES NO
YES
NO
Chart No. 3 - Thermostat is calling for heat. Burner motor runs for
about 30-45 seconds. System does not attempt to ignite.
First, check combustion chamber for excess oil.
NOTE: After ignition control is reset, you will have 30 SECONDS
to perform the tests shown below before the controller locks out.
Reset ignition control:
Press the RED BUTTON,
hold for three seconds, and release. DO NOT
RESET MORE THAN ONE TIME.
Transformer and Electrode Checks:
Measure voltage between transformer/primary lead
and neutral connection. Check transformer, insulators,
and electrodes.
The secondary terminals of a good transformer de-
liver 5000 volts arc to ground, for a total of 10,000
volts between terminals. Measure this with a trans-
former tester or use a well insulated screwdriver to
draw an arc across the two springs. This should be at
least 3/4” in length.
Check each secondary output terminal by drawing a
strong arc between the spring and base. If the arc is
erratic, weak, or unbalanced between the two termi-
nals, replace the transformer.
Replace electrodes when the tips become worn or
eroded.
Replace any insulators that are questionable.
Transformer failures and ignition problem can be
caused by the following:
Excessive gap on the ignition electrodes. Gap
should be 3/32”.
High ambient temperatures
High humidity
Carbon residue on the porcelain bushings
Low input line voltage
Arcing between the ignition electrodes and
the transformer springs. They must have good
contact.
Carbon residue, moisture, crazing or pin holes
on the insulators
Improper positioning of nozzle in relation to
the radius of the end cone
Carbon residue on electrode parts
Vue de la page 41
1 2 ... 37 38 39 40 41 42 43 44 45 46 47 ... 51 52

Commentaires sur ces manuels

Pas de commentaire