Form I-RA/D 140/235 (Version A), Mfg No. 110318 Rev 3, Page 41
Troubleshooting
Continued
Check for line
voltage across Terminals
5 and 2. Is voltage
read?
Check for line
voltage across Terminals
13 and 11. Is voltage
read?
*Is burner
motor reset button
tripped?
Reset and check
for proper
operation.
Replace burner
motor.
Replace fuse.
Replace ignition
controller.
YES
NO
YES
NO
YES
NO
Chart No. 2 - Thermostat calling for heat,
burner motor never attempts to run (green
light is lit) indicating “System Ready”. Chart
No. 1 has been successfully completed.
NOTE: After ignition control is reset, you will have 30 SECONDS to per-
form the tests shown below before the controller locks out.
Reset ignition control:
Press the RED BUTTON, hold for four seconds,
and release. DO NOT RESET MORE THAN ONE TIME.
*Reset button on the motor activates when the motor is overheated.
Motor amp draw must be less than the full load amps on the motor
rating plate. Verify the motor is operating correctly.
Refer to illustration
on page 38.