Form I-RA/D 140/235 (Version A), Page 46
Fan and Limit Controls
Model RA/RAD 140 and 235 heaters are equipped with a fan control and
limit control assembly consisting of a specially designed control mounting
bracket with a fan control, a circulating air high limit control, and a super
high limit control attached. To access the fan and limit control assembly,
remove the plate as illustrated. For service information, see Troubleshoot-
ing Chart 6, page 45.
The main functions of the fan/blower control are to provide:
Delay of fan or blower operation, preventing circulation of cold air
at startup.
Continued fan or blower operation as long as the unit temperature
is above minimum setting. The fan/blower control also provides
additional safety control by keeping the fan or blower in operation
in the event that a malfunction would cause the oil burner to
continue to fire when the thermostat is satisfied.
The circulating air high limit switch is nonadjustable and automatically
cycles when the internal temperature exceeds the setpoint. For the heater to
operate properly and safely, the cause for the temperature exceeding the
high limit setpoint must be corrected.
The super high limit switch provides redundant control and is calibrated
to open at a much higher temperature (350°F) than the standard automatic
reset limit switch indicates a major failure caused by a malfunction of the
primary safety controls or miswiring. Before attempting to re-start the heater
the cause must be corrected and the fan and limit control assembly re-
placed.
Troubleshooting
Continued
Remove plate to
access fan and limit
control assembly.
Circulating Air
High Limit
Super High
Limit
Fan/Blower
Control